Skip to product information
1 of 7

VTSYIQI

VTSYIQI Power Quality Analyzer Meter 3-Phase Power Quality Analyzer Energy Analyzer with Small Sharp Current Clamp 8mm×15mm Current Clamp 10mA to 10.0A Real-time Waveform USB 150 groups Data Records for Electric Power Railroad Quality Analysis

VTSYIQI Power Quality Analyzer Meter 3-Phase Power Quality Analyzer Energy Analyzer with Small Sharp Current Clamp 8mm×15mm Current Clamp 10mA to 10.0A Real-time Waveform USB 150 groups Data Records for Electric Power Railroad Quality Analysis

Regular price $2,565.00 USD
Regular price Sale price $2,565.00 USD
Sale Sold out
Shipping calculated at checkout.

VTSYIQI Power Quality Analyzer Meter 3-Phase Power Quality Analyzer Energy Analyzer with Small Sharp Current Clamp 8mm×15mm Current Clamp 10mA to 10.0A Real-time Waveform USB 150 groups Data Records for Electric Power Railroad Quality Analysis

Feature:

Three-phase power analyzer Data * Real-time waveform display (4 cannleotvoltage/current) * True RMS values of voltages and currents. * Peak current and voltage * The maximum/minimum value of current and voltage over a period of time * Pharos diagram display * Harmonic measurement of each phase, up to the 50th harmonic * Calculation of Total Harmonic Distortion (THD) * Active/reactive/apparent power value and total value of each phase * Transformer K factor calculation

3-phase power analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on. Can simultaneously measure the 4-channel current (ABC three phase and neutral wire current), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period

3 phase power quality analyzer is a comprehensive test instrument specially designed by our company for three-phase, inr-functional, intelligent and simple man-machine operation Easy to use, large LCD color display, high resolution, bilingual interface in Chinese and Enalish. box structureandotherfaaturessimultaneousmeasurementof4 currents(ABC three-ohase and minimum vaoues voltages (ABC three -phase vollale and neutral to ground vollael current and vollage peaks, maximum reactive power, apparent power, power factor, displacement power factor, active energy, reactive energy, apparent energy,rarimonic ratio, total harmonic distortion Degree

Energy quality analyzer In the current power applications, more and more large power equipment, power grid fault have become more and more complex, with development of the industry, it put forward high request more and more to quality that electric energy. We provide this power quality analyzer for that, which you can troubleshoot of complex power system more quickly and accurate, and monitoring and maintenance of power quality parameters more comprehensive and systemic.

Power quality analyzer adopt DSP + ARM double processor architecture, DSP is use for data collection and the processing of algorithm, the ARM is use for the communication protocol and the man-machine interface processing; Analog signal acquisition is by 2 pieces ADC Chip of ADI company. Resolution for ADC Chip is 16 bit and it is 4 channel synchronous sampling. Power Quality Analyzer also named: Intelligent Three Phase Power Quality Analyzer, Multifunctional Power Quality Analyzer, which simultaneous with the functions of harmonic Analyzer, phase volt-ampere meter, electric parameter tester. It apply to electricity industry

 

Introduction:

This Power Quality Analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation.

It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on.

Can simultaneously measure the 4-channel current (ABC three phase and neutral wire current), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, total harmonic distortion and harmonic, etc;

Display real-time waveform, harmonic ratio bar charts of current voltage; Dynamically capture instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.

In the current power applications, more and more large power equipment, power grid fault have become more and more complex, with development of the industry, it put forward high request more and more to quality that electric energy.

We provide this power quality analyzer for that, which you can troubleshoot of complex power system more quickly and accurate, and monitoring and maintenance of power quality parameters more comprehensive and systemic.

This Power quality analyzer adopt DSP + ARM double processor architecture, DSP is use for data collection and the processing of algorithm, the ARM is use for the communication protocol and the man-machine interface processing;

Analog signal acquisition is by 2 pieces ADC Chip. Resolution for ADC Chip is 16 bit and it is 4 channel synchronous sampling. The highest sampling rate can reach 1 MSPS, to ensure the accuracy of the channel and the information integrity, and wouldn’t miss any transient changes in the grid, can more accurate to detect the transient waveform rising and dropping drastically, and waveform instantaneous interrupt;

DSP working frequency is over 200 MHZ, to be able to timely monitoring of the power grid and dynamically adjust the sampling frequency to realize synchronization of power frequency and sampling frequency;

Using a 5.6 -inch LCD color screen display, a resolution of 640 dots x 480 dots, with different display color difference between the parameters of phase, waveform, vector diagram, harmonic ratio, the user can be more efficient and more intuitive understand the state of power grid parameters.

Built-in flash memory can store 60 group of screenshots at the same time, 150 groups of capture transient voltage/current waveform figure, and 12800 groups of alarm list. Starting current detection model can continuously capture starting current waveform for 100 s.

Built-in 2G memory card to store the trend curve record, simultaneous recording 20 parameters (can choose according to need) collect data for once every five seconds, trend curve records can be stored for 300 days.

Power Quality Analyzer also named: Intelligent Three Phase Power Quality Analyzer, Multifunctional Power Quality Analyzer, which simultaneous with the functions of harmonic Analyzer, phase volt-ampere meter, electric parameter tester.

It apply to electricity industry, petrochemical, metallurgy, railway, mining enterprises, scientific research institution, metrology department. Especially suitable for comprehensive analysis and diagnosis on all the voltage, current, power, power, harmonic, phase electric parameters.

 

Specification:

 

Power supply:Rechargeable lithium-ion battery packs 9.6V, backup charger.

Battery indicator:Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute.

Power consumption:Current consumption of normal test 490 mA, continuous working for 10 hours.

Display mode:LCD color screen, 640dots×480dots, 5.6 inches, display domain: 116mm×88mm.

Size of clamp:small sharp current clamp: 8mm×15mm

Instrument dimensions:L×W×H: 277.2mm × 227.5mm × 153mm.

Number of channels:4U/4I.

Phase-to phase voltage:1.0V~2000V.

Phase-to-neutral voltage:1.0V~1000V.

Current:current clamp: 10mA~10.0A

 

 

  1. True RMS current:10mA~99mA;Max error of true RMS current:±(1%+3dgt); Max error of phase angleφ:±(1.5°),Arms≥20mA
  2. True RMS current:100mA~10.0A;Max error of true RMS current:±(1%+3dgt); Max error of phase angleφ:±(1°)

 

 

Frequency:40Hz~70Hz.

Parameters of electricity:W, VA, Var, PF, DPF, cosφ, tanφ.

Energy parameters:Wh, Varh, Vah.

Harmonic:Order 0~50.

Total harmonic distortion:Order 0~50, each phase.

Expert mode:Yes.

Number of Transient records:150 sets.

Voltage flicker:Yes.

Starting current mode:Yes, 100 seconds.

3 phases unbalance:Yes.

Record:300 days(simultaneous recording 20 parameters, record one point every 5 seconds).

Min/Max recorded value:Measurement of maximum and minimum values over a period of time.

Alarm:40 different types of parameter selections, 12,800 sets alarm logs.

Peak:Yes.

Phasor diagram display:Automatically.

Capacity of snapshots:60.

 

 

Menu language:English/Chinese.

Communication:USB.

Automatic switching off:When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off.;In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute.

Backlight function:Yes, suitable for use at night and dark place.

Weight:Host: 1.6kg (with battery).;small sharp current clamp: 168g×4;Test wires and power adapter: 800g;Total weight: about 10.8kg (with packaging).

Length of voltage test wire:3m.

Length of current sensor wire:2m.

Working temperature and humidity:-10°C~40°C; below 80%Rh.

Storage temperature and humidity:-10°C~60°C; below 70%Rh.

Input impedance:Input impedance of test voltage: 1MΩ.

Withstand voltage:Withstand 3700V/50Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell.

Insulation:Between instrument wiring and shell ≥10MΩ.

Structure:Double insulation, with insulation vibration-proof sheath.

Safely rules:IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.

Note: current clamp and instruments must be connected to the corresponding,cannot be inserted opposite.